Industrial Control & Automation Solution – Honeywell SZR-LY2-N1 100VAC | SZR Series General Purpose Relay
Where This Product Is Used
The Honeywell SZR-LY2-N1 100VAC is a DPDT (Double Pole Double Throw) general purpose relay engineered for demanding industrial switching applications. It is widely deployed in the following environments and systems:
- PLC Output Interface Circuits – Acts as an interposing relay between PLC digital output cards and field devices, protecting sensitive PLC I/O modules from inductive load surges.
- Machine Control Panels – Used in motor starter auxiliary circuits, conveyor control systems, and packaging machinery to switch 100VAC control signals reliably.
- HVAC & Building Automation – Controls compressor contactors, fan motors, and damper actuators in commercial HVAC systems where 100VAC coil voltage is standard.
- Process Control Systems – Integrated into DCS (Distributed Control System) marshalling cabinets for signal isolation and load switching in oil & gas, chemical, and water treatment plants.
- Safety Interlock Circuits – Deployed in emergency stop (E-stop) relay logic and safety interlock panels where reliable coil energization at 100VAC is required.
- Food & Beverage Processing Equipment – Installed in washdown-rated control panels for conveyor drives, filling machines, and labeling systems.
- Semiconductor & Electronics Manufacturing – Used in test fixtures and automated handling equipment requiring precise, low-bounce switching.
Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | Honeywell |
| Part Number / SKU | SZR-LY2-N1 100VAC |
| Series | SZR Series (General Purpose Relay) |
| Coil Voltage | 100VAC (50/60 Hz) |
| Contact Configuration | DPDT (2 Form C) – 2 NO + 2 NC |
| Contact Rating | 10A @ 250VAC / 10A @ 30VDC |
| Terminal Type | 8-Pin Octal Base (Plug-in) |
| Coil Power Consumption | Approx. 1.6VA (AC) |
| Insulation Resistance | ≥100 MΩ (500VDC) |
| Dielectric Strength | 2,000VAC (coil to contact) |
| Mechanical Life | 10,000,000 operations (min.) |
| Electrical Life | 100,000 operations @ rated load |
| Operating Temperature | -40°C to +70°C |
| Mounting | Plug-in socket (compatible with SZR-LY2 series sockets) |
| Weight | Approx. 50g |
Note: Specifications are based on Honeywell published datasheets. Always verify against the official datasheet for your specific application.
Why Engineers Specify This Model
- 100VAC Coil Voltage – Specifically designed for Japanese-standard 100VAC control circuits, making it the preferred choice for Japanese OEM machinery and equipment exported globally.
- DPDT Contact Architecture – Two independent switching circuits in a single relay body reduce panel space and wiring complexity compared to using two SPDT relays.
- Octal Plug-in Base – Tool-free replacement in the field; the relay body can be swapped without rewiring, minimizing downtime during maintenance.
- Honeywell SZR Series Reliability – The SZR series is a globally recognized platform with decades of proven performance in harsh industrial environments.
- Wide Temperature Range – Operates reliably from -40°C to +70°C, suitable for both outdoor enclosures and high-ambient-temperature machine rooms.
- High Dielectric Strength – 2,000VAC coil-to-contact isolation ensures safe operation in mixed-voltage control panels.
Complete System Bill of Materials
For a complete relay installation using the SZR-LY2-N1 100VAC, the following compatible components are typically required:
- Relay Socket – Honeywell SZR-SY08 or equivalent 8-pin octal socket (DIN rail or panel mount)
- Relay Socket with LED Indicator – SZR-SY08-E (with built-in LED and diode)
- DIN Rail – Standard 35mm DIN rail (EN 50022)
- Terminal Blocks – Phoenix Contact or Weidmüller 2.5mm² screw terminal blocks for field wiring
- Surge Suppressor – RC snubber or MOV suppressor across coil terminals for inductive load protection
- Fuse Holder – 10A rated inline fuse for contact circuit protection
Contact support@konmask.com for a complete BOM quotation including sockets and accessories.
Compliance & Industry Standards
- UL Listed (File No. per Honeywell certification)
- CE Marked – Compliant with EU Low Voltage Directive (LVD) and EMC Directive
- RoHS Compliant – Restriction of Hazardous Substances
- IEC 61810-1 – Electromechanical elementary relays standard
- REACH Compliant
Quality Assurance & Sourcing
At Konmask.com, every Honeywell SZR-LY2-N1 100VAC relay we supply undergoes a rigorous multi-point verification process before shipment:
- Authenticity Verification – All units are sourced from authorized Honeywell distributors or verified OEM surplus channels. Counterfeit detection checks are performed on every batch.
- Visual Inspection – Housing integrity, label legibility, pin condition, and date code verification.
- Functional Test – Coil energization at rated voltage and contact continuity verification using calibrated test equipment.
- Packaging Inspection – Original or equivalent ESD-safe packaging to prevent transit damage.
- Documentation – Certificate of Conformance (CoC) and test reports available upon request.
How to Source This Part
- Submit an Inquiry – Email support@konmask.com or call +0086 19859288691 with your required quantity and delivery timeline.
- Receive a Quote – Our team will respond within 24 business hours with pricing, lead time, and availability confirmation.
- Order Confirmation – Confirm your purchase order. We accept T/T bank transfer, PayPal, and other B2B payment methods.
- Inspection & Dispatch – Parts are inspected, packed, and shipped via DHL, FedEx, or UPS with full tracking.
- After-Sales Support – Our engineering team provides post-delivery technical support and warranty assistance.
Application-Specific FAQ
- Q: Can the SZR-LY2-N1 100VAC be used with a 110VAC control circuit?
- A: The rated coil voltage is 100VAC. While some tolerance exists (typically ±10%), operating at 110VAC continuously may reduce coil life. For 110VAC applications, specify the SZR-LY2-N1 110VAC variant instead.
- Q: What socket is compatible with the SZR-LY2-N1?
- A: The SZR-LY2-N1 uses an 8-pin octal base and is compatible with Honeywell SZR-SY08 series sockets. Ensure the socket is rated for your panel’s DIN rail or surface-mount configuration.
- Q: Is this relay suitable for DC load switching?
- A: Yes. The contacts are rated for 10A @ 30VDC. For higher DC voltages, consult the derating curves in the Honeywell datasheet, as DC arcing characteristics differ from AC.
- Q: What is the minimum order quantity (MOQ)?
- A: Konmask.com supports orders from a single unit. Volume pricing is available for orders of 10 units or more. Contact us for a tiered pricing schedule.
- Q: Do you provide a Certificate of Conformance?
- A: Yes. A CoC is available for all orders upon request at no additional charge.
- Q: What is the typical lead time?
- A: In-stock items ship within 1–3 business days. For larger quantities or special sourcing requirements, lead time is typically 5–15 business days. Contact us for current stock status.
© 2026 Konmask.com. All rights reserved.
Original Source: https://Konmask.com
Contact: support@konmask.com | +0086 19859288691
{
“@context”: “https://schema.org/”,
“@type”: “Product”,
“name”: “Honeywell SZR-LY2-N1 100VAC General Purpose Relay”,
“description”: “Honeywell SZR-LY2-N1 100VAC DPDT 8-pin octal plug-in general purpose relay, 10A contact rating, SZR Series, for industrial PLC control panels and automation systems.”,
“sku”: “SZR-LY2-N1 100VAC”,
“brand”: {
“@type”: “Brand”,
“name”: “Honeywell”
},
“manufacturer”: {
“@type”: “Organization”,
“name”: “Honeywell”
},
“category”: “General Purpose Relay”,
“url”: “https://konmask.com/products/honeywell-szr-ly2-n1-100vac-general-purpose-relay-szr-series”,
“offers”: {
“@type”: “Offer”,
“url”: “https://konmask.com/products/honeywell-szr-ly2-n1-100vac-general-purpose-relay-szr-series”,
“priceCurrency”: “USD”,
“availability”: “https://schema.org/InStock”,
“seller”: {
“@type”: “Organization”,
“name”: “Konmask.com”
}
}
}
{
“@context”: “https://schema.org”,
“@type”: “FAQPage”,
“mainEntity”: [
{
“@type”: “Question”,
“name”: “Can the SZR-LY2-N1 100VAC be used with a 110VAC control circuit?”,
“acceptedAnswer”: {
“@type”: “Answer”,
“text”: “The rated coil voltage is 100VAC. While some tolerance exists (typically ±10%), operating at 110VAC continuously may reduce coil life. For 110VAC applications, specify the SZR-LY2-N1 110VAC variant instead.”
}
},
{
“@type”: “Question”,
“name”: “What socket is compatible with the SZR-LY2-N1?”,
“acceptedAnswer”: {
“@type”: “Answer”,
“text”: “The SZR-LY2-N1 uses an 8-pin octal base and is compatible with Honeywell SZR-SY08 series sockets.”
}
},
{
“@type”: “Question”,
“name”: “Is this relay suitable for DC load switching?”,
“acceptedAnswer”: {
“@type”: “Answer”,
“text”: “Yes. The contacts are rated for 10A @ 30VDC. For higher DC voltages, consult the derating curves in the Honeywell datasheet.”
}
},
{
“@type”: “Question”,
“name”: “What is the minimum order quantity (MOQ)?”,
“acceptedAnswer”: {
“@type”: “Answer”,
“text”: “Konmask.com supports orders from a single unit. Volume pricing is available for orders of 10 units or more.”
}
},
{
“@type”: “Question”,
“name”: “Do you provide a Certificate of Conformance?”,
“acceptedAnswer”: {
“@type”: “Answer”,
“text”: “Yes. A CoC is available for all orders upon request at no additional charge.”
}
},
{
“@type”: “Question”,
“name”: “What is the typical lead time?”,
“acceptedAnswer”: {
“@type”: “Answer”,
“text”: “In-stock items ship within 1–3 business days. For larger quantities or special sourcing requirements, lead time is typically 5–15 business days.”
}
}
]
}