GE IC697PWR724 Power Supply | Replacement, Equivalent & Selection Guide
The GE IC697PWR724 is a high-reliability AC input power supply module designed for the GE Fanuc Series 90-70 PLC rack system. Rated at 120/240 VAC input with regulated DC outputs, it powers the CPU, I/O modules, and communication cards within the 90-70 backplane. This page provides full technical specifications, verified compatible replacements, application guidance, and sourcing information to help engineers and procurement teams make confident decisions.
Technical Specifications
- Part Number: IC697PWR724
- Manufacturer: GE Fanuc / General Electric
- Series: Series 90-70 PLC
- Input Voltage: 120/240 VAC, 47–63 Hz
- Output: +5 VDC, +12 VDC, −12 VDC (backplane regulated)
- Power Rating: 90 W total output
- Form Factor: Single-slot module, Series 90-70 rack-mount
- Operating Temperature: 0°C to 60°C
- Weight: Approx. 1,480 g
- Certifications: UL, CE (original GE unit)
- Status: Legacy / End-of-Life (OEM); aftermarket and refurbished stock available
Compatible Replacement & Equivalent Models
When the IC697PWR724 is unavailable or cost-prohibitive, the following models are verified drop-in or functionally equivalent replacements for Series 90-70 racks:
- IC697PWR711 — GE Series 90-70, 120 VAC input, 55 W; suitable for lighter-load racks
- IC697PWR748 — GE Series 90-70, 24 VDC input; use when AC input is unavailable
- IC697PWR720 — Earlier revision of the 724; functionally compatible, verify firmware revision
- IC697PWR730 — Higher-capacity 120 W variant; backward-compatible with 90-70 racks requiring more headroom
- Third-party equivalents — Select industrial PSU vendors offer form-fit-function replacements; contact Konmask for vetted options
Note: Always verify rack slot compatibility and total load calculation before substituting power supply modules.
Why Choose the Original Model
- Guaranteed backplane compatibility — Designed specifically for Series 90-70 mechanical and electrical interface
- Proven field reliability — Widely deployed in process control, utilities, and manufacturing since the 1990s
- OEM firmware alignment — No risk of communication or diagnostic mismatch with GE CPUs
- Regulatory compliance — Original UL/CE certifications intact for audited facilities
- Reduced integration risk — No re-validation required in certified safety or process environments
Typical Applications
- Oil & gas pipeline SCADA and DCS integration
- Power generation and substation automation
- Water/wastewater treatment plant control
- Automotive and heavy manufacturing assembly lines
- Chemical process control with legacy GE 90-70 infrastructure
- Spare parts inventory for plant maintenance and MRO programs
System Compatibility
- Rack: GE Series 90-70 (IC697CHS750, IC697CHS782, IC697CHS790, and variants)
- CPUs: IC697CPU731, IC697CPU771, IC697CPU781, IC697CPU782, IC697CPU788, IC697CPU789
- I/O Modules: All standard Series 90-70 discrete and analog I/O modules
- Communication: IC697CMM711, IC697CMM741, IC697BEM711, and other 90-70 network modules
- Not compatible with: Series 90-30, VersaMax, PACSystems RX3i/RX7i (different form factor and bus)
Selection Guide
Use the following criteria to select the correct power supply for your Series 90-70 system:
- Step 1 — Calculate total rack load: Sum the current draw of all installed modules (CPU + I/O + comms). Refer to GE datasheet GFK-0356 for per-module consumption values.
- Step 2 — Match input voltage: IC697PWR724 requires 120/240 VAC. If your panel supplies 24 VDC, select IC697PWR748 instead.
- Step 3 — Confirm rack slots: The PWR724 occupies one dedicated power supply slot; verify your rack model has a compatible slot.
- Step 4 — Check redundancy requirements: For redundant power configurations, two PSU modules and a compatible rack are required.
- Step 5 — Evaluate refurbished vs. new: For non-critical spares, tested refurbished units offer significant cost savings. For critical uptime applications, request new or factory-reconditioned stock.
Quality Assurance & Sourcing
- All units sourced by Konmask undergo incoming inspection and functional testing prior to shipment
- Refurbished units are tested to OEM electrical specifications with documented test reports available on request
- Traceability documentation (COC, test records) provided for regulated industries
- Secure anti-static packaging with ESD-safe handling throughout the supply chain
- 90-day warranty on all refurbished units; 12-month warranty on new/factory stock
How to Order
- Online: Add to cart directly from this page
- Email RFQ: support@konmask.com — include part number, quantity, and required delivery date
- Phone/WhatsApp: +0086 19859288691
- Lead time: In-stock units ship within 1–3 business days; sourced units typically 5–10 business days
- Export: We support international orders with commercial invoice, packing list, and HS code documentation
Replacement & Compatibility FAQ
Q: Can I use IC697PWR711 instead of IC697PWR724?
A: Yes, if your total rack load is within the 55 W rating of the PWR711. Calculate your load first — the PWR724’s 90 W headroom is needed for fully populated racks.
Q: Is IC697PWR724 compatible with PACSystems RX7i?
A: No. The RX7i uses a different backplane and power supply form factor. You need IC698PSA100 or IC698PSA350 for RX7i systems.
Q: Can I run two IC697PWR724 modules for redundancy?
A: Yes, with a compatible redundant-power rack. Consult GE documentation GFK-0356 for wiring and configuration details.
Q: Do you supply test reports with refurbished units?
A: Yes. Functional test reports are available upon request for all refurbished stock.
Q: What is the lead time for out-of-stock units?
A: Typically 5–10 business days for sourced units. Contact us for urgent requirements.