GE IS230SNRTH2A / IS200SRTDH2ACB RTD Input Module | Replacement, Equivalent & Selection Guide
The GE IS230SNRTH2A and IS200SRTDH2ACB are RTD (Resistance Temperature Detector) input modules designed for use in General Electric Mark VI / Mark VIe turbine control systems. These modules provide high-accuracy temperature signal conditioning for industrial gas turbines, steam turbines, and generator control applications. This page serves as a comprehensive selection, replacement, and compatibility reference for procurement engineers and automation specialists.
Technical Specifications
- Part Numbers: IS230SNRTH2A / IS200SRTDH2ACB
- Manufacturer: General Electric (GE Energy / GE Vernova)
- Function: RTD (Resistance Temperature Detector) Input Signal Conditioning
- Compatible RTD Types: PT100, PT200, PT500, PT1000 (IEC 60751); Ni100, Ni120
- Input Channels: Multi-channel RTD input (refer to GEH series documentation for channel count)
- Communication Interface: IONet (GE proprietary I/O network)
- Form Factor: VME / Mark VI I/O board
- Operating Temperature: 0°C to +60°C
- Power Supply: 28 VDC (supplied via Mark VI I/O rack)
- Weight: Approx. 600 g
- Approvals: CE, UL (per GE system certification)
- Firmware: Compatible with Mark VI / Mark VIe control platform firmware
Compatible Replacement & Equivalent Models
The following modules are known compatible replacements or functional equivalents. Always verify firmware revision and rack slot compatibility before substitution:
- IS200SRTDH2A — Direct hardware revision equivalent (H2A vs H2ACB suffix denotes PCB revision)
- IS200SRTDH1A — Earlier hardware revision; verify firmware compatibility
- IS230SNRTH1A — Prior revision of IS230SNRTH2A; functionally equivalent in most Mark VI configurations
- DS200SRTDH1A — Legacy DS200 series equivalent for older Mark V / Mark VI hybrid racks
- IS215SRTDH2A — Mark VIe platform variant; confirm IONet addressing before use
- Third-party equivalents: Consult Konmask technical team for vetted aftermarket alternatives with OEM-equivalent performance
Note: Part number suffixes (A, B, C, H1, H2) indicate hardware revisions. Functional compatibility must be confirmed against your system’s Bill of Materials (BOM) and GE configuration tool (ToolboxST).
Why Choose the Original Model
- OEM Accuracy: Factory-calibrated to GE Mark VI system tolerances — no field recalibration required
- Firmware Integrity: Pre-loaded with GE-certified firmware; plug-and-play replacement in existing racks
- Diagnostic Support: Full integration with GE ToolboxST for online diagnostics, fault logging, and trending
- Long Service Life: Industrial-grade components rated for continuous 24/7 operation in harsh environments
- Warranty & Traceability: Sourced with full traceability documentation; eligible for GE service contracts
Typical Applications
- Gas turbine exhaust temperature monitoring (EGT / TXX channels)
- Steam turbine bearing and casing temperature measurement
- Generator stator winding temperature protection
- Compressor inlet and inter-stage temperature sensing
- Heat recovery steam generator (HRSG) temperature control loops
- Combined cycle power plant DCS integration via Mark VIe
System Compatibility
- GE Mark VI — Primary platform; full compatibility confirmed
- GE Mark VIe — Compatible with IS215 / IS230 series I/O racks; verify slot assignment
- GE Mark V — Not directly compatible; DS200 series required for Mark V racks
- Third-party DCS integration: Requires GE IONet gateway; not a standalone Modbus/PROFIBUS device
- ToolboxST Version: Compatible with ToolboxST v04.02 and above
Selection Guide
Use the following criteria to select the correct RTD input module for your application:
- Step 1 — Identify your control platform: Mark VI (IS200/IS230 series) vs. Mark VIe (IS215 series) vs. Mark V (DS200 series)
- Step 2 — Confirm RTD sensor type: PT100 (most common), PT200, Ni100, or custom range
- Step 3 — Check hardware revision: Match H1/H2 suffix to your existing rack BOM to avoid firmware conflicts
- Step 4 — Verify channel count: Confirm number of RTD input channels required per I/O rack slot
- Step 5 — Review firmware version: Use GE ToolboxST to confirm minimum firmware version supported by your controller
- Step 6 — Contact Konmask: Our technical team can cross-reference your system serial number and BOM to confirm the exact compatible part
Quality Assurance & Sourcing
- All units sourced from authorized distributors or verified surplus channels with full traceability
- Pre-shipment functional testing available on request (burn-in test report provided)
- Anti-counterfeit inspection: PCB markings, date codes, and component authenticity verified
- Packaging: ESD-safe anti-static bags with foam cushioning; export carton with shock indicators
- Documentation: Certificate of Conformance (CoC), test report, and original GE datasheet included
- Warranty: 12-month replacement warranty against manufacturing defects
How to Order
- Online: Add to cart directly on this page — stock availability shown in real time
- RFQ / Bulk Orders: Email support@konmask.com with quantity, required delivery date, and destination country
- Phone / WhatsApp: +0086 19859288691 (Mon–Fri, 09:00–18:00 CST)
- Lead Time: In-stock units ship within 1–3 business days; sourced units 7–21 business days
- Shipping: DHL Express, FedEx International, or sea freight for bulk orders; export documentation included
- Payment: T/T (wire transfer), PayPal, credit card via Shopify Payments
Replacement & Compatibility FAQ
Q: Can IS200SRTDH2ACB replace IS230SNRTH2A directly?
A: In most Mark VI rack configurations, yes — both perform the same RTD input function. However, confirm the slot address and firmware revision in ToolboxST before hot-swapping in a live system.
Q: Is this module compatible with PT100 sensors only?
A: No. The module supports multiple RTD types including PT100, PT200, PT500, PT1000, and Ni100/Ni120. Configuration is done via ToolboxST software.
Q: Can I use a third-party replacement instead of the OEM part?
A: Third-party equivalents exist and may be cost-effective for non-critical applications. Konmask can advise on vetted aftermarket options. For safety-critical turbine protection loops, OEM parts are strongly recommended.
Q: Do you provide a test report with the module?
A: Yes. Functional test reports are available on request. Please specify when placing your order or RFQ.
Q: What is the lead time for out-of-stock units?
A: Sourced units typically require 7–21 business days depending on origin. Contact us for a firm delivery commitment before placing a time-sensitive order.
Q: Can you supply multiple units for a plant overhaul?
A: Yes. We handle bulk procurement for planned outages and plant overhauls. Contact us for volume pricing and consolidated shipping options.
© 2026 Konmask.com. All rights reserved.
Original Source: https://Konmask.com
Contact: support@konmask.com | +0086 19859288691