Siemens 6EP1336-3BA10 – 24VDC/10A Stabilized Power Supply | SITOP PSU100M Platform
Engineering Background
The SITOP PSU100M series represents Siemens’ mid-range industrial power supply platform, engineered for demanding automation environments where reliable DC power delivery is non-negotiable. The 6EP1336-3BA10 is the 10 A variant of this series, designed to bridge the gap between basic SITOP compact units and the full-featured SITOP modular family — delivering diagnostics, wide-range input, and robust output stability in a single DIN-rail package.
Product Positioning
Targeted at machine builders, panel integrators, and plant engineers who require a cost-effective yet diagnostics-capable 24 V supply for SIMATIC S7-300/400/1200/1500 PLCs, distributed I/O, HMI panels, and field instrumentation. The PSU100M occupies the sweet spot between price and functionality in Siemens’ SITOP portfolio.
Complete Technical Specifications
| Order Number | 6EP1336-3BA10 |
| Series | SITOP PSU100M |
| Input Voltage (AC) | 120 – 230 V AC (wide-range), 50/60 Hz |
| Input Voltage Range | 93 – 132 V AC / 186 – 264 V AC |
| Input Current | ≤ 2.5 A @ 120 V AC / ≤ 1.3 A @ 230 V AC |
| Output Voltage (DC) | 24 V DC (adjustable 22.8 – 26.4 V) |
| Output Current | 10 A (continuous) |
| Output Power | 240 W |
| Output Ripple & Noise | < 150 mV peak-to-peak |
| Efficiency | ≥ 89% @ full load, 230 V AC |
| Power Factor Correction | Active PFC (EN 61000-3-2 compliant) |
| Inrush Current Limiting | Electronic soft-start |
| Hold-up Time | ≥ 20 ms @ 230 V AC, full load |
| Overload Behavior | Hiccup mode; auto-recovery |
| Short-Circuit Protection | Electronic, auto-restart |
| Overvoltage Protection | Yes (output clamp) |
| Diagnostic Output | Floating relay contact (DC OK signal), LED status indicator |
| SFB Technology | Selective Fuse Breaking — up to 6× rated current for 12 ms to blow downstream fuses |
| Parallel Operation | Supported (for redundancy or increased current) |
| Ambient Temperature | -25 °C to +70 °C (operating); -40 °C to +85 °C (storage) |
| Relative Humidity | 5 – 95%, non-condensing |
| Degree of Protection | IP20 |
| Mounting | DIN rail (EN 60715 TH35) |
| Dimensions (W × H × D) | 55 × 125 × 120 mm |
| Weight | approx. 900 g |
| Certifications | CE, UL 508, cULus, GL, ATEX Zone 2, IECEx |
| EMC Compliance | EN 61000-6-2 (immunity), EN 61000-6-4 (emission) |
| MTBF | > 500,000 hours @ 40 °C (IEC 61709) |
Proven Application Environments
- SIMATIC PLC Panels: Primary 24 V rail supply for S7-300, S7-400, S7-1200, and S7-1500 CPU and I/O modules
- Distributed I/O: ET 200SP, ET 200M, ET 200S field station power
- HMI & Operator Panels: SIMATIC HMI Basic/Comfort panels, TP/KP series
- Drive Auxiliaries: Control voltage supply for SINAMICS G120/S120 auxiliary circuits
- Process Instrumentation: Transmitters, solenoid valves, field sensors in process plants
- Safety Systems: Auxiliary supply for SIMATIC Safety F-CPUs and F-I/O (non-safety rail)
- Harsh Environments: Outdoor enclosures, marine panels, ATEX Zone 2 classified areas
- Redundant Architectures: Parallel with SITOP diode modules (6EP1961-2BA00) for N+1 redundancy
Engineering Advantages
- SFB (Selective Fuse Breaking): Delivers up to 6× rated current for 12 ms — ensures downstream branch fuses blow cleanly without tripping the main supply, preserving system uptime
- Wide-Range AC Input: Single unit covers 120 V and 230 V grids globally — no manual voltage selection switch, eliminating mis-wiring risk
- Active PFC: Reduces harmonic distortion on the AC supply, compliant with EN 61000-3-2 Class A — critical for facilities with strict power quality requirements
- DC OK Relay Contact: Floating signal contact enables direct integration with PLC digital inputs for power-fail alarming and controlled shutdown sequences
- Extended Temperature Range: -25 °C to +70 °C operation — suitable for unheated outdoor enclosures and high-ambient machine rooms without derating
- Parallel Capability: Two units can be paralleled for 20 A output or N+1 redundancy without additional ORing hardware (use with SITOP diode module for true redundancy)
- Compact 55 mm Width: Narrow DIN-rail footprint maximizes panel density in space-constrained enclosures
- High MTBF: >500,000 hours at 40 °C — reduces unplanned maintenance intervals and lifecycle cost
System Architecture & Signal Flow
The 6EP1336-3BA10 operates as a single-stage power conversion unit with the following internal signal chain:
- AC Input Stage: EMC filter → inrush limiter → bridge rectifier → bulk capacitor (PFC-corrected)
- DC/DC Conversion: High-frequency PWM switching (LLC resonant topology) → transformer isolation → synchronous rectification
- Output Regulation: Closed-loop voltage regulation with ±1% static accuracy; output adjustable via front-panel trimmer (22.8 – 26.4 V)
- Protection Layer: Overload detection → hiccup mode → auto-restart; OVP clamp; thermal shutdown with auto-recovery
- Diagnostics: DC OK comparator → relay driver → floating contact output (terminals 11/12); green LED on front panel
- SFB Circuit: Current-boost circuit activates on short-circuit detection, delivers 6× IN for ≤12 ms, then enters hiccup mode
Wiring note: L/N/PE on terminals 1/2/3 (AC input); +24V/0V on terminals 4/5 (DC output); DC OK relay on terminals 11/12. Torque: 0.8 N·m for power terminals.
Sourcing & Quality Verification
- Origin: Genuine Siemens product, sourced through authorized industrial distribution channels
- Condition: New-in-box (NIB) or factory-refurbished units clearly labeled — no mixed-condition listings
- Verification: Each unit inspected against Siemens product label (order number, date code, serial number) before dispatch
- Counterfeit Risk Mitigation: Siemens holographic label, PCB markings, and firmware version verified where applicable
- Documentation: Siemens datasheet and EU Declaration of Conformity available on request
- Warranty: 12-month Konmask operational warranty; Siemens OEM warranty terms apply for NIB units
Procurement Process
- Confirm Specification: Verify input voltage (120/230 V AC), output requirement (24 V / 10 A / 240 W), and certifications needed (UL, ATEX, etc.)
- Request Quote: Contact support@konmask.com for volume pricing (>5 units), lead time confirmation, and export documentation
- Place Order: Add to cart and complete checkout — or submit a purchase order via email for NET-30 B2B accounts
- Shipping: Ships within 1–3 business days from Hong Kong warehouse; DHL Express / FedEx International available; export-controlled items may require EUC
- Incoming Inspection: Recommended: verify order number label, check output voltage at no-load and full-load, confirm DC OK relay operation before panel installation
Technical FAQ
Q: Can the 6EP1336-3BA10 replace the older 6EP1336-2BA10?
A: Yes. The 3BA10 is the PSU100M-generation successor to the 2BA10 (PSU100C). Electrical ratings are identical (24 V/10 A); the 3BA10 adds SFB technology, active PFC, and the DC OK relay contact. Mounting footprint is compatible.
Q: Is derating required above 60 °C ambient?
A: No derating is required up to 70 °C. Above 60 °C, ensure minimum 50 mm clearance above and below the unit for convection airflow. Forced cooling is not required but extends service life.
Q: Can two units be paralleled for 20 A without a diode module?
A: Parallel operation is supported for load sharing. For true N+1 redundancy (one unit fails, the other carries full load without interruption), use the SITOP diode module 6EP1961-2BA00 to prevent reverse current flow.
Q: What is the DC OK relay contact rating?
A: The floating relay contact is rated 24 V DC / 1 A. It closes when output voltage is within the regulation window and opens on fault — suitable for direct connection to a PLC digital input.
Q: Is this unit suitable for ATEX Zone 2 installations?
A: The 6EP1336-3BA10 carries ATEX II 3 G certification, permitting installation in Zone 2 (occasionally explosive atmosphere) when mounted in a suitable enclosure rated for the zone.
Q: What is the inrush current at switch-on?
A: Electronic soft-start limits inrush to ≤ 20 A peak at 230 V AC, allowing use of standard C-curve MCBs (minimum 16 A recommended for the AC branch).
© 2026 Konmask.com. All rights reserved.
Original Source: https://Konmask.com