The TC-HAO081 is a field-proven analog output module developed by Honeywell for its Experion PKS (Process Knowledge System) and TotalPlant Solution (TPS) distributed control platforms. Designed to meet the rigorous demands of continuous process industries, this module bridges the DCS controller layer with field instrumentation via the HART (Highway Addressable Remote Transducer) protocol, enabling simultaneous analog control and digital diagnostics over a single twisted-pair loop.
Product Positioning
Procurement engineers specifying replacement or expansion I/O for Honeywell Experion C200/C300 controllers, Safety Manager, or legacy TPS cabinets will find the TC-HAO081 a direct, drop-in compatible solution. Its 8-channel density, HART pass-through capability, and hot-swap design minimize process interruption during maintenance windows — a critical requirement in refinery, petrochemical, and power generation environments.
Complete Technical Specifications
- Part Number: TC-HAO081
- Manufacturer: Honeywell Process Solutions
- Module Type: Analog Output, HART-enabled
- Channel Count: 8 channels (isolated)
- Output Signal: 4–20 mA (sourcing)
- HART Protocol: HART 5 / HART 7 compatible, multi-drop capable
- Resolution: 16-bit DAC per channel
- Accuracy: ±0.1% of full scale
- Loop Compliance Voltage: Up to 750 Ω load
- Isolation: Channel-to-channel and channel-to-bus isolation
- Power Consumption: Supplied via backplane (C200/C300 chassis)
- Operating Temperature: 0°C to +60°C
- Storage Temperature: −40°C to +85°C
- Humidity: 5–95% RH, non-condensing
- Weight: 220 g
- Form Factor: Single-slot I/O module, hot-swappable
- Certifications: CE, UL, FM; SIL 2 capable (with Safety Manager integration)
- Compatible Platforms: Honeywell Experion PKS C200, C300; TotalPlant Solution (TPS); Safety Manager
- SKU / Order Code: TC-HAO081
Proven Application Environments
- Oil & Gas: Upstream wellhead control, midstream pipeline regulation, downstream refinery unit operations
- Petrochemical & Chemical: Reactor temperature/pressure control loops, distillation column management
- Power Generation: Boiler feed water control, turbine governor interfaces, combined-cycle plant I/O expansion
- Pulp & Paper: Digester pressure control, bleach plant flow regulation
- Pharmaceuticals: Batch reactor control, clean-room HVAC valve positioning
- Water & Wastewater: Pump speed reference output, dosing valve control
Engineering Advantages
- HART Transparency: Full HART command pass-through allows field device configuration, diagnostics, and calibration without loop interruption — compatible with AMS Device Manager and Field Device Tool (FDT) frameworks.
- Hot-Swap / Online Replacement: Module can be removed and reinserted under power without controller shutdown, reducing MTTR and supporting zero-downtime maintenance strategies.
- High Channel Density: 8 isolated outputs per slot maximizes cabinet real estate utilization in brownfield expansions.
- Diagnostic Transparency: Per-channel open-loop, short-circuit, and out-of-range diagnostics reported to the Experion operator station in real time.
- SIL-Capable Architecture: When integrated with Honeywell Safety Manager, the module supports SIL 2 safety instrumented functions per IEC 61511.
- Backward Compatibility: Fully interoperable with legacy TPS/TDC 3000 migration projects using Honeywell’s Universal I/O strategy.
System Architecture & Signal Flow
The TC-HAO081 resides in a standard Honeywell I/O chassis (IOTA) and communicates with the C200 or C300 controller via the FTE (Fault Tolerant Ethernet) backplane. Each of the 8 output channels independently sources a 4–20 mA signal to the field device. The HART modem embedded in each channel superimposes a 1200/2200 Hz FSK digital signal on the analog loop, enabling bidirectional digital communication with HART-capable field instruments (control valves, positioners, variable-speed drives) without interrupting the primary analog control signal.
Signal path: Controller setpoint → Backplane → TC-HAO081 DAC → 4–20 mA loop → Field actuator / HART device
Sourcing & Quality Verification
- Origin: Genuine Honeywell Process Solutions hardware; sourced through authorized industrial distribution channels.
- Condition: New surplus or factory-refurbished units available; each unit undergoes functional loop test prior to shipment.
- Documentation: Honeywell datasheet, firmware revision label, and test report available upon request.
- Traceability: Serial number and date code recorded at dispatch; full chain-of-custody documentation available for regulated industries.
- Warranty: 12-month operational warranty against manufacturing defects; DOA replacement within 7 business days.
Procurement Process
- Step 1 — Verify Compatibility: Confirm your chassis type (C200 / C300 / TPS IOTA) and firmware revision. Contact our technical team with your controller model if uncertain.
- Step 2 — Request Quote: Submit your BOM or part number list via support@konmask.com or WhatsApp +0086 19859288691 for volume pricing and lead-time confirmation.
- Step 3 — Order & Payment: Purchase orders accepted; T/T bank transfer, PayPal, and trade-finance terms available for qualified accounts.
- Step 4 — Shipping: DHL / FedEx express worldwide; EXW Xiamen or CIF destination available. Export documentation (CO, packing list, commercial invoice) included.
- Step 5 — Incoming Inspection: We recommend loop-test verification upon receipt. Our technical team provides remote commissioning support at no additional charge.
Technical FAQ
Q: Is the TC-HAO081 compatible with Experion R500 and later releases?
A: Yes. The module is supported across Experion PKS R400 through R520 and later. Confirm IOIM firmware compatibility with your site’s Experion release notes.
Q: Can I use this module in a Safety Manager chassis?
A: The TC-HAO081 is a standard process I/O module. For SIL-rated safety output, it must be used within a validated Safety Manager I/O configuration. Consult Honeywell’s Safety Manual for the applicable SIL claim limit.
Q: What is the difference between TC-HAO081 and TC-HAO082?
A: The TC-HAO081 is the standard 8-channel HART analog output module. The TC-HAO082 is the redundant-capable variant. Verify your system’s redundancy architecture before substituting.
Q: Do you provide a Certificate of Conformance (CoC)?
A: Yes. CoC, functional test report, and serial number traceability documentation are available upon request for all shipments.
Q: What is the minimum order quantity?
A: No minimum order quantity. Single-unit orders are accepted. Volume discounts apply for orders of 5+ units.
© 2026 Konmask.com. All rights reserved.
Original Source: https://Konmask.com
Contact: support@konmask.com | +0086 19859288691